NVO5-111 Warning Device for Containers and Tanks
主要优势一览
- 230 V AC supply voltage
- Two independent, potential-free change-over contacts
- Visual and acoustic alarm
- Connection to central monitoring system
- Easy installation on DIN rail
显示详情



注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
NVO5-111 技术数据
| Connection | terminals 5, 6, 7 | |
| Rated voltage | Ur | 230 V AC ± 10 %, 50/60 Hz |
| Fusing | max. 10 A | |
| Power consumption | 6 VA |
| Display elements | LED SUPPLY (power supply), one yellow LED LED SYSTEM OK (indication operating status), one green LED LED ALARM (alarm active), one yellow LED LED SENSOR FAILURE (sensor fault), one red LED | |
| Control elements | button ALARM RESET: reset of the alarm relays and of the acoustic alarm |
| Surge protection | overvoltage category III |
| Connection | input 1: sensors KVF/NVF terminals 13+, 15- input 2: ON/OFF switch terminals 22+, 24- |
| Connection | output 1: terminals 1, 2, 3; output 2: terminals 10, 11, 12 | |
| Output | relay , volt-free change-over contact | |
| Contact loading | 250 V AC/4 A/100 VA |
| Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff | |
| Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Galvanic isolation | EN 50178 | |
| Degree of protection | IEC 60529 |
| Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
| Degree of protection | IP20 | ||||||||||
| Mass | approx. 325 g | ||||||||||
| Dimensions | 70 x 86 x 58 mm (2.8 x 3.4 x 2.3 inch) | ||||||||||
| |||||||||||
| Mounting | DIN rail, system M36 | ||||||||||
| EU-type examination certificate | BVS 09 ATEX E 137 | ||||||||||||||||||||||
| |||||||||||||||||||||||
| Supply | |||||||||||||||||||||||
| |||||||||||||||||||||||
| Output | |||||||||||||||||||||||
| |||||||||||||||||||||||
| Directive conformity | |||||||||||||||||||||||
| |||||||||||||||||||||||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |