选择您所在的国家/地区
停售
KFD2-ELD-Ex16 Ground Fault Detection
24 V DC
主要优势一览
- 16-channel isolated barrier
- 24 V DC supply (Power Rail)
- Analog or digtial field device inputs
- Monitors leakage current
- Fault relay contact output
- LED status indication
- Test circuit for validation
- Parallel connection for easy integration
- Conformal coating
显示详情



注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
- ES
- FR
- PL
KFD2-ELD-Ex16 技术数据
| Signal type | Analog input |
| Connection | Power Rail or terminals 44+, 45- | |
| Rated voltage | Ur | 20 ... 30 V DC |
| Ripple | ≤ 10 % | |
| Rated current | Ir | ≤ 50 mA |
| Connection side | field side | |
| Connection | intrinsically safe: terminals 1 ... 16 non-intrinsically safe: terminals 28, 29 | |
| Ground connection | terminal 17 | |
| Rated values | 5 Vpp, 0.1 mA; rectangular | |
| Function | Test input: 24 V DC / 5 mA; non-polarized |
| Connection side | control side | |
| Connection | terminals 19, 20, 21 | |
| Output | signal ; relay | |
| Contact loading | 253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load; | |
| Mechanical life | 107 switching cycles |
| Response delay | ≤ 50 s |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs | |
| Control elements | DIP switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 | ||||||||||
| Connection | screw terminals | ||||||||||
| Mass | approx. 260 g | ||||||||||
| Dimensions | 60 x 119 x 115 mm (2.4 x 4.7 x 4.5 inch) (W x H x D) , housing type D2 | ||||||||||
| |||||||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||||||
| EU-type examination certificate | TÜV 00 ATEX 1585 | |||||||||||||
| ||||||||||||||
| Supply | ||||||||||||||
| ||||||||||||||
| Collective error message | ||||||||||||||
| ||||||||||||||
| Galvanic isolation | ||||||||||||||
| ||||||||||||||
| Directive conformity | ||||||||||||||
| ||||||||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |