FB9215B2 Power Supply
主要优势一览
- Multi range power supply 90 ... 253 V AC
- Suitable for the supply of 24 I/O modules and 1 bus coupler
- Use two power supplies for redundancy
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
显示详情






注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
FB9215B2 技术数据
| Bus coupler | 2 | |
| I/O modules | >12, depending on the type |
| Connection | wired to Ex e terminals via backplane | |
| Maximum safe voltage Um | 253 V AC |
| Input voltage range | 90 ... 253 V AC | |
| Input frequency | 50 ... 60 Hz | |
| Inrush current (< 2 ms) | 30 A max. (115 V AC) 50 A max. (230 V AC) | |
| Current consumption | 0.95 A (115 V AC) 0.6 A (230 V AC) |
| Voltage | 5.4 V DC +/- 5% , 12 V DC +/- 3% | |
| Power | P5V ≤ 5.4 W, P12V ≤ 39 W - P5V | |
| Power dissipation | approx. 18 % of power consumption |
| LED indication | LED green: OFF in case of loss of main power or internal voltages (12 V, 5.4 V) |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Environmental test | EN 60068-2-14:2009 | |
| Shock resistance | EN 60068-2-27:2009 | |
| Vibration resistance | EN 60068-2-6:2008 | |
| Damaging gas | EN 60068-2-42:2003 | |
| Relative humidity | EN 60068-2-78:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | ||||||||||
| Mass | approx. 890 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| EU-type examination certificate | PTB 97 ATEX 1074 U | ||||
| |||||
| Galvanic isolation | |||||
| |||||
| Directive conformity | |||||
| |||||
| ATEX approval | PTB 97 ATEX 1074 U | ||||
| IECEx approval | |||||
| |||||
| System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
相关页面