选择您所在的国家/地区
LB8107H0706 Com Unit
Com unit for Modbus RTU
主要优势一览
- Interface between the I/O modules and the PCS/PLC
- Com unit for 80 analog or 184 digital channels
- Communication via MODBUS RTU
- Mounting in Zone 2, Class I/Div.2 or in the safe area
- HART communication via service bus
- Configuration via FDT 1.2 DTM
- Non-volatile memory for configuration and parameter settings
- Self configuration in redundant systems
- Permanently self-monitoring
- Outputs drive to safe state in case of failures
- Module can be exchanged under voltage
显示详情






注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
LB8107H0706 技术数据
| Connection | backplane bus | |
| Rated voltage | Ur | 5 V DC , only in connection with the power supplies LB9*** |
| Power dissipation | 1.8 W | |
| Power consumption | 1.8 W |
| Fieldbus type | MODBUS RTU | |||||||
| MODBUS RTU | ||||||||
| ||||||||
| Number of stations per bus line | max. 245 (MODBUS), max. 119 (service bus) | |||||||
| Number of channels per station | max. 80 analog, max. 184 digital (standard configuration) | |||||||
| Number of stations per bus segment | max. 31 (RS-485 standard) | |||||||
| Number of repeaters between Master and Slave | max. 3 | |||||||
| Supported I/O modules | all LB remote I/O modules | |||||||
| Bus length | max. 1200 m (FOL, 38.4 kBd), max. 1200 m (copper cable, 38.4 kBd) | |||||||
| FOL (fiber optic link) | additional hardware required | |||||||
| Addressing | via configuration software | |||||||
| MODBUS address | standard compliant (factory standard setting: 126) | |||||||
| Service bus address | max. 119 , redundancy address = base + 128 (automatic) | |||||||
| HART communication | via service bus | |||||||
| Redundancy | system dependent | |||||||
| Connection | backplane bus | |
| Redundancy | via backplane |
| LED indication | LED P: (power supply): On = operating, fast flash = cold start LED 1: (collective alarm): On = internal fault, flashing = no fieldbus connection LED 2: (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation LED 3: (status fieldbus): flashing = fieldbus receive channel active LED 4: (status fieldbus): flashing = fieldbus response channel active LED 5: (status service bus): flashing = service bus receive channel active LED 6: (status service bus): flashing = service bus response channel active |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Environmental test | EN 60068-2-14 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Damaging gas | EN 60068-2-42 | |
| Relative humidity | EN 60068-2-78 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Altitude | max. 2000 m | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 (module) , mounted on backplane | ||||||||||
| Connection | via backplane | ||||||||||
| Mass | approx. 120 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Certificate | PF 08 CERT 1234 X | ||||
| |||||
| Directive conformity | |||||
| |||||
| ATEX approval | PF 08 CERT 1234 X | |||||||
| UL approval | E106378 | |||||||
| IECEx approval | ||||||||
| ||||||||
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. | |