选择您所在的国家/地区
PSU1200-J2-DC-N0 Power Supply
Power supply, apparatus for direct current operation of explosion-protected equipment in hazardous areas
主要优势一览
- Certified for ATEX and IECEx Zone 2/22
- Galvanic isolation between input and output
- Provides an output power up to 80 W at 24 V DC
- Fully IP66 rated






注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
PSU1200-J2-DC-N0 技术数据
| Input voltage | 18 ... 36 V DC (SELV/PELV acc. IEC 60950-1) | |
| Input current | max. 5.5 A/2.7 A |
| Output current | max. 3.3 A | |
| Voltage | 24 V DC (SELV) | |
| Power | 80 W with derating | |
| Power dissipation | 17 W at 80 W output power |
| Electromagnetic compatibility | |||||
| |||||
| RoHS | |||||
| |||||
| Operating temperature | -20 ... 65 °C (-4 ... 149 °F) with derating | |
| Storage temperature | -20 ... 65 °C (-4 ... 149 °F) | |
| Relative humidity | 93% at 40°C, non-condensating, according to EN60068-2-78 | |
| Shock resistance | 18 shocks 15 g , 11 ms all axis, IEC 60068-2-27 |
| Core cross section | max. 2.5 mm2 (14 AWG) | ||||
| Degree of protection | IP66 | ||||
| Material | |||||
| |||||
| Mass | approx. 2.5 kg | ||||
| Dimensions | 245 mm x 122 mm x 42 mm | ||||
| EU-type examination certificate | BVS 16 ATEX E 097 X | ||||
| |||||
| Directive conformity | |||||
| |||||
| IECEx approval | IECEx BVS 16.0063X | |||||||
| ||||||||