选择您所在的国家/地区

转至全球网站

M-LB-4400 Fault Status Module

主要优势一览

  • Monitoring of up to 50 surge protection barriers
  • Two-part monitoring device
  • Device set with transmitter/receiver and reverse unit
  • Fault indication via LED
  • Status indication output

显示详情

Product Compliance: Europe – CE
Approval symbol
Approval symbol
Product Compliance: China – CCC
注意

在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。

EN
  • EN
  • DE
  • ES
  • FR
  • PL

M-LB-4400 技术数据

Voltage range6 ... 35 V DC
Rated currentIr≤ 10 mA
Connectionterminals 11, 12
Switching power48 V DC/500 mA/Pmax 300 mW
Outputsignal ; remote signalling contact (NC contact)
Leakage current< 1 µA
Resistorcontact resistance : < 2.5 Ω
Test cyclecontinuous
Display elementsstatus display
operating state (green)
fault indication (red)
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Relative humiditymax. 95 % , without condensation
Corrosion resistanceacc. to ISA-71.04, severity level G3
Degree of protectionIP20
Connectionspring terminals with push-in connection technology
Core cross section0.2 ... 2.5 mm2 one wire
0.2 ... 2.5 mm2 fine-strand
Material
HousingPolyamide PA 6.6
Massapprox. 52 g
Dimensions6 x 90 x 69 mm (0.24 x 3.5 x 2.7 inch) (W x H x D)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
CertificateTÜV 22 ATEX 8882 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 , EN IEC 60079-7:2015+A1:2018
UL approvalE223772
IECEx approval
IECEx certificateIECEx TUR 22.0052X
IECEx markingEx ec IIC T4 Gc
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
一般说明