HiC5861 Relay Module
主要优势一览
- 1-channel signal conditioner
- 24 V DC supply (loop powered)
- Logic input 19 V DC ... 27.6 V DC
- Relay contact output for de-energized to safe function
- Test pulse immunity
- Up to SIL 3 acc. to IEC/EN 61508
- Up to PL e acc. to EN/ISO 13849
显示详情






注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
- ES
- FR
- PL
HiC5861 技术数据
| Signal type | Digital Output |
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e |
| Connection | loop powered | |
| Rated voltage | Ur | 19 ... 30 V DC loop powered |
| Power dissipation | < 1.3 W | |
| Power consumption | < 1.3 W |
| Connection side | control side | |
| Connection | Input SL1: 8a(+), 7a(-) ; test input SL1: 3a(-), 3b(+), 4a(+), 4b(+) | |
| Pulse/Pause ratio | 150 ms / 150 ms | |
| Test pulse length | max. 4 ms from DO card | |
| Test input | see functional safety manual | |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 27.6 V | |
| Rated voltage | Ur | 19 ... 27.6 V loop powered |
| Rated current | Ir | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
| Connection side | field side | |
| Connection | SL2: 5a, 5b | |
| Contact loading | 30 V DC/1 A resistive load | |
| Minimum switch current | 10 mA / 24 V DC | |
| Energized/De-energized delay | 150 ms / 150 ms | |
| Mechanical life | 2 x 107 switching cycles | |
| Fuse rating | 1.5 A |
| Switching frequency | < 3 Hz |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff | |
| Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff |
| Display elements | LEDs | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Machinery Directive | |||||
| |||||
| Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 | |
| Degree of protection | IEC 60529:2013 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
| Degree of protection | IP20 | ||||||||||
| Mass | approx. 100 g | ||||||||||
| Dimensions | 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D) | ||||||||||
| |||||||||||
| Mounting | on termination board | ||||||||||
| Coding | no pin trimmed For further information see system description. | ||||||||||
| Certificate | PF 17 CERT 4192 X | ||||
| |||||
| Directive conformity | |||||
| |||||
| UL approval | E106378 |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |