Teknisk support Industrielle sensorer
Kundeservice, eksplosjonsbeskyttelse

Inductive sensor NCB10-30GM40-N0-15M

NCB10-30GM40-N0-15M
  • 10 mm flush
  • Stainless steel housing


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datablad utdrag: Tekniske data for  NCB10-30GM40-N0-15M

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance10 mm
Installationflush
Assured operating distance0 ... 8.1 mm
Actual operating distance9 ... 11 mm typ.
Reduction factor rAl 0.35
Reduction factor rCu 0.3
Reduction factor r304 0.75
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 200 Hz
Hysteresis1 ... 15 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detectedmin. 2.2 mA
Measuring plate detected≤ 1 mA
Switching state indicatorall direction LED, yellow
Functional safety related parameters
MTTFd1870 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0037X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level Dc (tc)IECEx TUR 21.0018X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GaPTB 00 ATEX 2048 X
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
Equipment protection level Dc (tc)TÜV 20 ATEX 8524 X
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0452
CCC approval
Hazardous Location2020322315002255
NEPSI approval
NEPSI certificateGYJ16.1393X
CML approvalon request
ANZEx18.3018X
KCC approval
Hazardous Location09-AV4BO-0226
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typecable
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP66 / IP67
Cable
Cable diameter6 mm ± 0.2 mm
Bending radius> 10 x cable diameter
MaterialPVC
Core cross section0.75 mm2
Length15 m
Dimensions
Length40 mm
Diameter30 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NCB10-30GM40-N0-15M

Documents: NCB10-30GM40-N0-15M

Instruction manualsFiltypeFilstørrelse
ИнструкцииPDF202 KB
Návod k poużitíPDF193 KB
Instruktions manualPDF191 KB
Instruction manualPDF193 KB
KasutusjuhendPDF186 KB
KäyttöohjePDF185 KB
Manuel d'instructionsPDF198 KB
BetriebsanleitungPDF192 KB
Οδηγίες χρήσηςPDF206 KB
HandleidingPDF192 KB
Instruction manual / BetriebsanleitungPDF190 KB
Használati útmutatóPDF196 KB
Manuale di istruzioniPDF194 KB
Lietošanas pamācībaPDF192 KB
Instrukciju vadovasPDF193 KB
Instrukcja obsługiPDF255 KB
Manual de instruçõesPDF196 KB
Manual de utilizarePDF196 KB
Návod na poużitiePDF194 KB
Navodila za uporaboPDF190 KB
Manual de instruccionesPDF197 KB
ManualPDF190 KB
Technical information
Installation conditionsPDF1054 KB
EinbaubedingungenPDF1060 KB

CAD+CAE: NCB10-30GM40-N0-15M

CADFiltypeFilstørrelse
CAD 3-D / CAD 3-DSTP51 KB
CAD Portal / CAD PortalLINK---

Approvals+Certificates: NCB10-30GM40-N0-15M

CertificatesFiltypeFilstørrelse
Australia AU Test Safe Group IPDF4026 KB
Canada USA UL Hazardous LocationPDF410 KB
Canada USA UL Ordinary LocationPDF288 KB
China SITIIAS CCC Ex CertificatePDF3704 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePDF12880 KB
Europe TUV Rheinland ATEX tc 3DPDF862 KB
Japan CML Ex iaPDF307 KB
KR KOSHA Ex iaPDF304 KB
United Kingdom CML UKEX Category I M2 UKEX Category II 2 G UKEX Category II 1 D UKEX Category II 1 GPDF541 KB
Worldwide PTB IECEx iaLINK---
Worldwide TUV Rheinland IECEx tcLINK---
Control Drawings
Control drawing UL / Control drawing ULPDF286 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)PDF1411 KB
EU Declaration of Conformity (P+F)PDF1408 KB
EU Declaration of Conformity (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1407 KB
UK Declaration of Conformity (P+F)PDF1381 KB
EU Declaration of Conformity (P+F)PDF1405 KB
EU Declaration of Conformity (P+F)PDF1404 KB
EU Declaration of Conformity (P+F)PDF1405 KB
EU-Konformitäterklärung (P+F)PDF1407 KB
EU Declaration of Conformity (P+F)PDF1412 KB
EU Declaration of Conformity (P+F)PDF1405 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1409 KB
EU Declaration of Conformity (P+F)PDF1405 KB
EU Declaration of Conformity (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1407 KB
EU Declaration of Conformity (P+F)PDF1408 KB
EU Declaration of Conformity (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1407 KB
EU Declaration of Conformity (P+F)PDF1408 KB
EU Declaration of Conformity (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1406 KB
EU Declaration of Conformity (P+F)PDF1405 KB
EU Declaration of Conformity (P+F)PDF1407 KB

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.