Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Faça o download das folhas de dados em PDF:
Folhas de dados: Dados técnicos do
RLK28-FC-55-Z/31/116
Descrição do Produto |
Compact fire protection photoelectric sensor |
General specifications |
Effective detection range | 1 ... 3 m |
Reflector distance | 1 ... 3 m |
Threshold detection range | 3 m |
Reference target | reflector C110-2 |
Light source | LED |
Light type | modulated visible red light , 660 nm |
Diameter of the light spot | approx. 50 mm at a distance of 3 m |
Opening angle | emitter 1.2° receiver 2° |
Ambient light limit | 80000 Lux |
Accessories provided | reflector C110-2 Bracket |
Functional safety related parameters |
MTTFd | 600 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Indicators/operating means |
Operation indicator | LED green |
Function indicator | 2 LEDs yellow, light up when light beam is free, flash when falling short of the stability control, off when light beam is interrupted |
Control elements | Time adjuster , Light-on/dark-on changeover switch |
Electrical specifications |
Operating voltage | 12 ... 240 V AC/DC |
Power consumption | ≤ 3.5 VA |
Output |
Switching type | light/dark on, switchable (selectable, light/dark switching is only activated if the receiver has 'dark on' selected.) |
Signal output | Relay, 1 alternator |
Switching voltage | max. 250 V AC/DC |
Switching current | max. 2 A |
Switching power | DC: max. 50 W AC: max. 500 VA |
Switching frequency | 25 Hz |
Response time | 20 ms |
Timer function | ON delay (GAN), OFF delay (GAB), one shot (IAB), ON delay-one shot (GAN-IAB), ON delay-OFF delay (GAN-GAB), programmable adjustment interval 0.1 ... 10 s |
Standard conformity |
Standards | EN 60947-5-2 smoke insensitive up to 2 dB/m ( EN 54-12 ) |
Approvals and certificates |
Protection class | II, rated insulation voltage ≤ 250 V AC with pollution degree 1-2 according to IEC 60664-1 Output circuit insulated from control circuit in accordance with IEC 61140. Caution! The protection class 2 is only valid when the terminal compartment is closed. |
CCC approval | Certified by China Compulsory Certification (CCC) |
Approvals | VdS/DIBt certificate of compliance No. 25022 , approval number Z-6.510-2384 |
Ambient conditions |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
Storage temperature | -40 ... 60 °C (-40 ... 140 °F) |
Relative humidity | 30% ... 85% non-condensing ; Non-icing |
Mechanical specifications |
Degree of protection | IP67 |
Connection | terminal compartment with 8 spring-loaded terminals for wire cross section 0.5 ... 1.5 mm2, insulation stripping 7.5 ... 8.5 mm, M16 x 1.5 cable gland |
Material | |
| Housing | plastic |
| Optical face | Plastic pane |
Mass | 112 g |
Dimensions | |
| Height | 88 mm |
| Width | 25.8 mm |
| Depth | 65.5 mm |
Classifications
System | Classcode |
ECLASS 13.0 | 27270902 |
ECLASS 12.0 | 27270902 |
ECLASS 11.0 | 27270902 |
ECLASS 10.0.1 | 27270902 |
ECLASS 9.0 | 27270902 |
ECLASS 8.0 | 27270902 |
ECLASS 5.1 | 27270902 |
ETIM 9.0 | EC002717 |
ETIM 8.0 | EC002717 |
ETIM 7.0 | EC002717 |
ETIM 6.0 | EC002717 |
ETIM 5.0 | EC002717 |
UNSPSC 12.1 | 39121528 |
Details:
RLK28-FC-55-Z/31/116
Product Documentation:
RLK28-FC-55-Z/31/116
Design / Simulation:
RLK28-FC-55-Z/31/116
Approvals:
RLK28-FC-55-Z/31/116
Produtos Relacionados:
RLK28-FC-55-Z/31/116
Accessories |
|
|
|
Mounting aid for round steel ø 12 mm or sheet 1.5 mm ... 3 mmfa |
|
|
|
|
Mounting bracket: mounting aid for sensors in the RL* seriesfa |
|
|
|
|
Mounting aid for RL* seriesfa |
|
|
|
|
Reflector, round ø 84 mm, central mounting holefa |
|