AS-Interface EMERGENCY STOP button |
General specifications |
Node type | Safety node |
AS-Interface specification | V3.0 |
Required gateway specification | ≥ V2.1 |
Profile | S-7.B |
| IO code | 7 |
| ID code | B |
| ID1 code | F |
| ID2 code | 0 |
UL File Number | E305142 |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Performance level (PL) | PL e |
Category | Cat. 4 |
Reaction time | < 300 µs |
MTTFd | no significant contribution to MTTFd of the overall system |
PFHd | no significant contribution to PFH of the overall system |
B10d | 250000 cycles |
Design lifetime | 20 a |
Indicators/operating means |
Button | |
| EMERGENCY STOP | illuminated |
Electrical specifications |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 80 mA |
Protection class | III |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) |
Rated insulation voltage | 32 V |
Pulse withstand voltage | 0.8 kV |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | IEC 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 A1:2011-02 EN 61326-1:2013 |
Machinery Directive | |
| Directive 2006/42/EC | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Electrical safety | IEC 61140:2009 |
Emitted interference | EN 61000-6-4:2007 A1:2011-02 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | IEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005 |
Functional safety | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017 |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 5000 m above MSL |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles |
Pollution degree | 2 |
Mechanical specifications |
Operating force | Push: 32 N Pull: 21 N Turn: 0.27 Nm Minimum for positive opening operation: 60 Nm |
Operating distance | for positive opening operation: min. 4 mm maximal: 4.5 mm |
Degree of protection | IP65
|
Connection | M12 round connector |
Material | |
| Housing | Polycarbonate |
Mass | 225 g |
Dimensions | |
| Height | 91.5 mm |
| Width | 76 mm |
| Length | 76 mm |
Life span | > 250,000 switching operations |
Classifications
System | Classcode |
ECLASS 13.0 | 27371244 |
ECLASS 12.0 | 27371244 |
ECLASS 11.0 | 27371244 |
ECLASS 10.0.1 | 27371244 |
ECLASS 9.0 | 27371244 |
ECLASS 8.0 | 27371244 |
ECLASS 5.1 | 27371228 |
ETIM 9.0 | EC002034 |
ETIM 8.0 | EC002034 |
ETIM 7.0 | EC002034 |
ETIM 6.0 | EC002034 |
ETIM 5.0 | EC002034 |
UNSPSC 12.1 | 39121533 |
Details:
VAA-2E1A-F85A/CB10-S-V1
Design / Simulation:
VAA-2E1A-F85A/CB10-S-V1
Approvals:
VAA-2E1A-F85A/CB10-S-V1
Produtos Relacionados:
VAA-2E1A-F85A/CB10-S-V1
Accessories |
|
|
|
Actuating protection for emergency off buttonfa |
|
|
|
|