Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

Zener Barrier SB8002

SB8002
  • 1-channel
  • DC version, positive polarity
  • Max. working voltage 10.6 V
  • Series resistance approx. 18.7 Ω
  • Fuse rating 100 mA
  • DIN rail mountable

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  SB8002

General specifications
TypeDC version, positive polarity
Electrical specifications
Series resistanceapprox. 18.7 Ω
Hazardous area connection
Connectionterminals 13, 23
Output voltageUin - 1.4 V at 75 mA
Safe area connection
Connectionterminals 11, 21
Working voltage9 ... 10.6 V
Short-circuit currentmax. 95 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Relative humidity< 95 % (30 d/year), no moisture condensation
Mechanical specifications
Degree of protectionIP20
Connectionscrew connection, max. 2.5 mm2
PA connection, max. 4 mm2
Massapprox. 100 g
Dimensions22.5 x 79 x 85.5 mm (0.88 x 3.11 x 3.36 inch) (W x H x D)
Height79 mm
Width22.5 mm
Depth88.5 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 16 ATEX 181955 X
MarkingEx-Hexagon II (2)G [Ex ib Gb] IIC
Ex-Hexagon II (2)D [Ex ib Db] IIIC
Ex-Hexagon I (M2) [Ex ib Mb] I
Voltage12.4 V
Current95 mA
Power1180 mW (rectangular characteristic curve)
Supply
Maximum safe voltage250 V AC / 125 V DC (Attention! Um is no rated voltage.)
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
IECEx approval
IECEx certificateIECEx TUN 16.0023 X
IECEx marking[Ex ib Gb] IIC
[Ex ib Db] IIIC
[Ex ib Mb] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027211016
ECLASS 12.027211016
ECLASS 11.027211016
ECLASS 10.0.127219001
ECLASS 9.027219001
ECLASS 8.027219001
ECLASS 5.127210702
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC002653
UNSPSC 12.139121018

Details: SB8002

Product Documentation: SB8002

Language Selection:
Safety and Security DocumentationLinguaFile tipoDimensioni
Instruction leaflet / BeipackzettelALLPDF257 KB

Approvals: SB8002

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
Europe TUV Nord II (2) D II (2) G ATEX Category MTÜV 16 ATEX 181955 XALLPDF285 KB
TUV Nord Ex ib IECEx Certificate of ConformityIECEx TUN 16.0023XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-2761AITAITAPDF188 KB