Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

Magnetic Immersion Probe for Continuous Measurement LMC-P

LMC-P
  • Sensor for continuous level measurement in liquids
  • Resolution 10 mm
  • Media contacting parts of plastic
  • Mounting without removing the float

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  LMC-P

General specifications
Equipment architectureA measuring system consists of a magnet-operated immersion probe LMC****-G6*-O4 and a signal converter S1SD-1TI-1U.
SeriesLMC-P
VersionsLMC10P6-G6P-O4
LMC10D5-G6D-O4
Output
Connection3-wire, potentiometer connection approx. 40 kΩ
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 , EN 61326-2-3:2013
Conformity
Degree of protectionIEC 60529:2000
Measurement accuracy
Accuracyresolution: 10 mm
Operating conditions
Process conditions
Process temperatureversion PP: -10 ... 80 °C (14 ... 176 °F)
version PVDF: -10 ... 100 °C (14 ... 212 °F)
Process pressure (static pressure)≤ 3 bar (43.5 psi)
Density≥ 0.8 g/cm3
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP66 / IP68
Connectionterminal box, 3 terminals , max. 2.5 mm2
Materialfloat, guide tube, process connection:
- version PP: PP (Polypropylene)
- version PVDF: PVDF (Polyvinylidenfluoride)
terminal box: Polyester
Dimensionsfloat:
- version PP: cylinder ∅55 mm x 54 mm
- version PVDF: cylinder ∅55 mm x 70 mm
guide tube: ∅14 mm, max. length 3000 mm
terminal box: 80 x 75 x 55 mm
Process connectionthread G2A to DIN/ISO 228/1
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Designation- LML-FD5 float, cylinder, Ø55 mm x 70 mm, PVDF
- LML-FP6 float, cylinder, Ø55 mm x 54 mm, PP

Classifications

SystemClasscode
ECLASS 13.027200502
ECLASS 12.027200502
ECLASS 11.027200502
ECLASS 10.0.127200502
ECLASS 9.027200502
ECLASS 8.027200502
ECLASS 5.127200502
ETIM 9.0EC001447
ETIM 8.0EC001447
ETIM 7.0EC001447
ETIM 6.0EC001447
ETIM 5.0EC001447
UNSPSC 12.141111950

Details: LMC-P

Product Documentation: LMC-P

Language Selection:
Safety and Security DocumentationLinguaFile tipoDimensioni
Manuale di istruzioniITAPDF46 KB
Manuals
Manual LMC-**ENGPDF835 KB

Approvals: LMC-P

Language Selection:
Declaration of ConformityCertificato NumeroLinguaFile tipoDimensioni
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2635ALLPDF64 KB
Contamination Declaration
Contamination declaration / Kontaminationserklärung   ALLPDF137 KB