Ultrasonic sensor UC4000-L2-I-V15

UC4000-L2-I-V15
  • Sensor head bidirectional and rotatable
  • Function indicators visible from all directions
  • Quick mounting bracket
  • Selectable sound lobe width
  • Programmable

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  UC4000-L2-I-V15

Descrizione prodotto
Single head system
General specifications
Sensing range200 ... 4000 mm
Adjustment range240 ... 4000 mm
Dead band0 ... 200 mm
Standard target plate100 mm x 100 mm
Transducer frequencyapprox. 85 kHz
Response delay≤ 180 ms
Indicators/operating means
LED greenOperating display
LED yellowobject in evaluation range
LED rederror
Electrical specifications
Operating voltage10 ... 30 V DC , ripple 10 %SS
No-load supply current≤ 50 mA
Interface
Interface typeSerial interface (programming adapter required)
9600 BPS, no parity, 8 data bits, 1 stop bit
Input/Output
Input/output type1 synchronization connection, bidirectional
0 Level0 ... 1 V
1 Level4 V ... UB
Input impedance> 12 kΩ
Output rated operating current< 12 mA
Pulse length0.5 ... 300 ms (level 1)
Pulse interval≥ 62.5 ms (level 0)
Synchronization frequency
Common mode operation≤ 16 Hz
Multiplex operation≤ 17 Hz / n , n = number of sensors , n ≤ 10
(factory setting: n = 5 )
Input
Input type1 program input
Level (evaluation limit 1)0 ... 1 V
Level (evaluation limit 2)4 V ... UB
Input impedance> 12 kΩ
Pulse length2 ... 10 s
Output
Output type1 analog output 4 ... 20 mA
ResolutionEvaluation range [mm]/3200, however ≥ 0.4 mm
Deviation of the characteristic curve≤ 0.2 % of full-scale value
Repeat accuracy≤ 0.1 % of full-scale value
Load impedance≤ 500 Ω at UB ≥ 14V
≤ 300 Ω at UB < 14V
Temperature influence≤ 1.5 % of full-scale value
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typeConnector M12 x 1 , 5-pin
Degree of protectionIP67
Material
HousingPA-GF35
Transducerepoxy resin/hollow glass sphere mixture; polyurethane foam
Mass120 g

CAD+CAE: UC4000-L2-I-V15

CADFile tipoDimensioni
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS1439 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP556 KB

Approvals+Certificates: UC4000-L2-I-V15

Statements of complianceCertificato NumeroFile tipoDimensioni
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0503CPDF241 KB
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0503APDF113 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
US CA UL General PurposeE87056LINK---

Software: UC4000-L2-I-V15

Device type managersinformazioni sulla liberatoriaFile tipoDimensioni
DTM for L2 and UMC3000 devices / DTM für Geräte der Serien L2 und UMC30001.2.0.9ZIP3979 KB
Software Tools
PACTware 4.1 SP5 / PACTware 4.1 SP54.1.0.52ZIP50675 KB
PACTware 5.0 / PACTware 5.05.0.4.20ZIP50037 KB

Prodotti associati : UC4000-L2-I-V15

Accessories

Female cordset, M12, 5-pin, PVC cablefa
Programming adapter, USB 2.0 interface, Simple insertion in the sensor connection leadfa
Programming unitfa
Software for connecting people, information, systems, and devices, For applications developed using .NET, Required to run PACTwareTMpa