Valve Coupler FD0-VC-EX4.PA

FD0-VC-EX4.PA
  • For four intrinsically safe valves with position sensors
  • Installation in Zone 1 and Zone 2
  • Valves in Zone 0
  • Connection to fieldbus acc. to FISCO or Entity
  • For PROFIBUS PA
  • PCS integration with FDT/DTM technology
  • Monitors lead breakage and short circuits
  • Valve monitoring and diagnostics integrated
  • Conducts partial stroke testing
  • Conforms to PROFIBUS PA profile

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Folhas de dados: Dados técnicos do  FD0-VC-EX4.PA

General specifications
Design / MountingOutside installation
Fieldbus connection
PROFIBUS PA
ConnectionConnection +, -
Rated voltage9 ... 32 V
Rated currentmax. 23 mA
Baud rate31.25 kBit/s
ProtocolIEC 61158-2
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Field circuit
Inputs
Connection8, for binary sensors: terminals 3, 4, 7, 8, 11, 12, 15, 16
Sensor supply voltage5 V
Sensor supply current5 mA
Time delay before availability2 ms
Max. cycle timemax. 160 ms
Outputs
Connectionterminals 1+, 2-; 5+, 6-; 9+, 10-; 13+, 14-
Output voltage6.4 ... 7.9 V
Output rated operating current1.5 mA
Holding current1 mA
Galvanic isolation
PROFIBUS PA/Field circuitsafe galvanic isolation acc. to EN 60079-11, voltage peak value 60 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Core cross sectionBus cable: ∅ 5 mm ... 10 mm
Cable sensors/valve: ∅ 4 mm ... 8 mm
Housing187 mm x 129 mm x 46 mm
Degree of protectionIP65
Installation positionCable glands downwards
Massapprox. 290 g
Mountingwall mounting
Data for application in connection with hazardous areas
EU-type examination certificatePTB 98 ATEX 2210
MarkingEx-Hexagon II 2G (1) Ex ia [ia Ga] IIC T4 Gb ,
Ex-Hexagon II (1D) [Ex ia Da] IIIC ,
Ex-Hexagon II 3G Ex ic IIC T4 Gc ,
Ex-Hexagon II (3D) [Ex ic Dc] IIIC
PROFIBUS PA
Voltage24 V
Current380 mA
Power5.32 W
Rated voltage9 ... 32 V
Rated current23 mA
FDE (Fault Disconnect Equipment)6.7 mA
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012
International approvals
IECEx approvalIECEx TUN 04.0002
Approved forEx ia [ia Ga] IIC T4 Gb ,
[Ex ia Da] IIIC ,
Ex ic IIC T4 Gc ,
[Ex ic Dc] IIIC
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: FD0-VC-EX4.PA

Datasheet: FD0-VC-EX4.PA

DatasheetTipo de ArquivoTamanho do Arquivo
Datasheet FD0-VC-EX4.PAPDF1730 KB
Datenblatt FD0-VC-EX4.PAPDF1716 KB

Approvals+Certificates: FD0-VC-EX4.PA

CertificatesTipo de ArquivoTamanho do Arquivo
Europe PTB II 2 G (1) II (1D) II (3D) II 3 G ATEXPDF1378 KB
TUV Nord IECEx Certificate of ConformityLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF88 KB

Software: FD0-VC-EX4.PA

Device DriverTipo de ArquivoTamanho do Arquivo
Device Driver / GerätetreiberZIP259 KB
GSD / GSDZIP4 KB
Software Tools
FD0-VC-Ex4.PA DTM / FD0-VC-Ex4.PA DTMZIP20003 KB

O Ethernet-APL permite a comunicação contínua em todos os níveis de hierarquia. Saiba mais sobre essa tecnologia pioneira...

Serviço de informações RSS sobre atualizações do PANOS

Seja informado(a) quando uma nova atualização do software PANOS, o sistema operacional dos comutadores Ethernet-APL, for lançada: Com nosso feed RSS, você receberá uma notificação por e-mail na sua caixa de entrada imediatamente após o lançamento de uma atualização.

Da decisão ao planejamento, da instalação ao comissionamento e da operação a manutenção: Saiba como aproveitar ao máximo a sua infraestrutura fieldbus!