Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Pobierz pełną kartę katalogową w formie pliku PDF:
Opis produktu |
---|
6500 series Ex pxb and Ex pyb purge and pressurization system |
General specifications | ||
---|---|---|
Operating mode | user programmable | |
Series | 6500 | |
System | ||
Number of volume exchanges | 5 to 19 | |
Hazardous environment | gas, dust, gas and dust | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Rated voltage | 100 ... 240 V AC, 48 ... 62 Hz / 0.2 A 20 ... 30 V DC |
|
Electrical specifications | ||
Connection | EPCU: Terminal blocks and grounding screw UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters Input type: intrinsically safe |
|
Interface | ||
Physical | Bluetooth® 4.1 | |
Transmitter frequency | 2.4 ... 2.4835 GHz | |
Transmitter radiated power | -19 ... 7.5 dBm | |
Sensitivity | -92.5 dBm at 0.1 % BER | |
Detection range | 100 m in air | |
Antenna | PCB | |
Communication | ||
Bluetooth | declaration ID: D037849 | |
Input | ||
Input I | Voltage free contact or namur proximity sensor | |
Input type | Intrinsically Safe, Ex ib | |
Input II | (1) 2-wire, PT100 RTD | |
Input type | Intrinsically Safe, Ex ib | |
Output | ||
Output I | AUX | |
Output type | Voltage free contact outputs, SPDT configuration | |
Inrush current | 2 A | |
Contact loading | 2 A @ 240VAC, resistive, 2 A @ 24VDC | |
Output II | Enclosure | |
Output type | Voltage free contact outputs, 2 N.O. configuration | |
Inrush current | 8 A | |
Contact loading | 8A @ 240 V AC, resistive up to 60 °C 8A @ 24 V DC up to 60 °C 5A @ 240 V AC, resistive, 60 to 70 °C 5A @ 24 V DC up to 60 to 70 °C |
|
Fuse | External fusing is required at no more than 11 amps/1500 A breaking current | |
Output III | Digital valve When used with the 6500-MAN-DV-01, intrinsically safe Internal resistance 280 Ω |
|
Output IV | Proportional valve When used with the 6500-MAN-PV-01, intrinsically safe Current: 4 to 20 mA Max. load: 300 Ω |
|
Communication | HART via RS485 (PACTware available) | |
Indicators/settings | ||
Display elements | 2x20 LCD for configuration, monitoring, and status of the 65000 system with back light and contrast selection. Capacitive touch buttons | |
LED indication | Safe pressure: Blue - safe pressure is achieved Enclosure power: Green - power on; Red - power off Rapid exchange: Blue - purging is running System bypass: Yellow - bypass is activated Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault Key: green - a button on the capacitive touch display has been activated. Momentary indication |
|
Pneumatic parameters | ||
Protective gas supply | instrument grade air or inert gas | |
Pressure requirement | For 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120 psig) regulated For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated Note: max. pressure will depend on the vent model used. |
|
Safe pressure | Gas: 0.82 mbar (0.33 in wc) Dust: 0.82 mbar (0.33 in wc) Gas+Dust: 0.82 mbar (0.33 in wc) |
|
Valve flows | Standard vent series: EPV-6500-*-01, 03, 05 Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm). Minimum and maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. Continuous (Dilution) vent series: EPV-6500-*-07, 08 Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading. Maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. |
|
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | 5 ... 85 %, non-condensing | |
Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes | |
Impact resistance | 30 g, 11 ms, all axes | |
Mechanical specifications | ||
Connection type | See mounting in 6500 manual and cable gland requirements | |
Cable gland | Cable gland requirement: cable glands are not included. Customer can supply their own approved glands or use one of the 6500-CBLG-... cable gland kits. I.S.cable glands: requires (5) M12 approved cable glands Power cable glands: requires (2) M16 and (2) M12 approved cable glands |
|
Degree of protection | IP66 | |
Material | UIC display: Makrolon FI cover and A380 Aluminum anodized casing Housing: 316L stainless steel Hardware: 316L stainless steel |
|
Mass | approx. 5 kg (11.0 lbs) | |
Dimensions | 6500-01-EXT1: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7") 6500-01-PM01: 150 x 150 x 185 mm (5.9" x 5.9" x 7.3") 6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7"), UIC: 150 x 150 x 45 mm (5.9" x 5.9" x 1.8") |
|
Height | 367.5 mm | |
Width | 183 mm | |
Depth | 152.5 mm | |
Data for application in connection with hazardous areas | ||
Certificate | DEMKO 16 ATEX 1640X | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-2:2014 , EN 60079-5:2015 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx UL 16.0003X | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27180508 |
ECLASS 12.0 | 27180508 |
ECLASS 11.0 | 27180508 |
ECLASS 10.0.1 | 27180508 |
ECLASS 9.0 | 27180508 |
ECLASS 8.0 | 27180508 |
ECLASS 5.1 | 40050501 |
ETIM 9.0 | EC000243 |
ETIM 8.0 | EC000243 |
ETIM 7.0 | EC000243 |
ETIM 6.0 | EC000243 |
ETIM 5.0 | EC000243 |
UNSPSC 12.1 | 39121301 |
The 6500 series purge and pressurization system consists of a control unit, an EPV-6500 enclosure protection vent, and a valve for pressurization, purging, and, with some models, dilution for analyzer applications.
The compact 6500 control unit features an LCD user interface with sealed capacitive touch buttons. LEDs provide quick indication of the system status. The control unit has an input for a 2-wire RTD for temperature control/monitoring. Models are available that allow the user interface to be panel mounted to an enclosure wall or mounted onto the exterior of the enclosure. A HART output allows the control unit to be connected to a PC using PACTware or the customer’s AMS for remote monitoring. An app for Android, BlackBerry, and Apple devices allows connectivity via Bluetooth®.
Literature | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Application Report - Hydrogen Analysis with Reliable Explosion Protection | ENG | 253 KB | |
Application Report - Label Printer Solution for Zone 1/21 and Zone 2/22 Applications | ENG | 135 KB | |
Application Report - Purge and Pressurization Solutions on FPSO Tankers | ENG | 351 KB |
Product information | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization" | ENG | 3860 KB | |
Brief Instructions | |||
Purge & Pressurization Smart App - Users Guide / Purge & Pressurization Smart App - Users Guide | ALL | 1771 KB | |
Safety and Security Documentation | |||
Instrukcja obsługi | POL | 164 KB | |
Manual | ENG | 1625 KB | |
Manuals | |||
Manual | ENG | 8336 KB |
CAD | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
2D / DXF Files for 6500 Series - external mount / CAD 2-D | ALL | ZIP | 258 KB |
CAD 2-D / CAD 2-D | ALL | ZIP | 1308 KB |
3D files for 6500 Series / 3-D-Modell für Serie 6500 | ALL | STP | 25244 KB |
Certificates | Nr. certyfikatu | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|---|
ATEX Certificate | DEMKO 16 ATEX 1640X | ALL | 488 KB | |
Bluetooth SIG Radio Approval | D037849 | ALL | LINK | --- |
China SITIIAS CCC Ex Certificate | 2020322304002485 (Katy, TX USA) | ALL | 1673 KB | |
IECEx Certificate of Conformity | IECEx UL 16.0003X | ALL | LINK | --- |
Korea KOSHA | 16-AV4BO-0186X | ALL | 1013 KB | |
UK-Type Examination Certificate | UL21UKEX2017X | ALL | 267 KB | |
Worldwide exida Functional Safety Certificate | P+F 1601040 P0006 C016 V1R1 | ALL | 124 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-B080C | ALL | 160 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-B0F7 | ALL | 156 KB |
Device Description Files/Drivers | Informacja o wersji | Typ pliku | Rozmiar pliku |
---|---|---|---|
DTM for 6500 Series / DTM_a | ZIP | 21548 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|