Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem
Niedostępne do zakupu
Niedostępne do zakupu

AS-Interface sensor/actuator module VAA-2EA-G4-ZE0/E0

VAA-2EA-G4-ZE0/E0
  • AS-Interface certificate
  • Degree of protection IP67
  • Flat or round cable connection (via standardized EEMS base, not included with delivery)
  • Cable piercing method or terminal compartment
    flat cable yellow/flat cable black or standard round cable
    inputs: PG7 screwed connection and cage-clamp terminals
  • Communication monitoring, turn-off
  • Power supply of outputs from the external auxiliary voltage
  • Power supply of inputs from the module
  • Function display for bus, inputs and outputs
  • Monitoring of sensor overloads

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  VAA-2EA-G4-ZE0/E0

Opis produktu
G4 PG module IP67
2 inputs (NPN) and 2 electronic outputs
General specifications
Node typeStandard node
Indicators/operating means
LED AS-idual LED green/red
green: AS-Interface voltage
red: communication error or address 0
green/red flashing: overload sensor supply
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 60 mA (without sensors) / max. 240 mA
Protection classIII
Input
Number/Type2 inputs for 2- or 3-wire sensors (NPN), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity≤ 180 mA (TB ≤ 40 °C),
≤ 140 mA (TB ≤ 60 °C), short-circuit protected
Input current≤ 8 mA (limited internally)
Switching point
0 (unattenuated)≤ 1.5 mA
1 (attenuated)≥ 4.5 mA
Output
Number/Type2 electronic outputs, NPN
Supplyfrom external auxiliary voltage UAUX
Current1.5 A per output
Voltage≥ (UAUX - 0.5 V)
Programming instructions
ProfileS-3.F
IO code3
ID codeF
Data bits (function via AS-Interface) input output
D0 IN1 -
D1 IN2 -
D2 - OUT3
D3 - OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring
P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP67 according to EN 60529
Connectioncable piercing method or terminal compartment
flat cable yellow/flat cable black or standard round cable
inputs/outputs: PG7 screwed connection and cage clamp terminals
Mass180 g
MountingDIN rail or screw mounting

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-2EA-G4-ZE0/E0

Design / Simulation: VAA-2EA-G4-ZE0/E0

Language Selection:
CADJęzykTyp plikuRozmiar pliku
CAD 3-D / CAD 3-DALLSTP2960 KB

Produkty powiązane: VAA-2EA-G4-ZE0/E0

Matching System Components

AS-Interface module mounting base with adressing jack for connection to flat cable (AS-Interface and external auxiliary power)fa
AS-Interface module mounting base for connection to flat cable (AS-Interface and external auxiliary power)fa
Accessories

AS-Interface Handheld with accessoryfa
Blind plug M12fa
Pobierz bezpłatnie: Opracowanie na temat protokołów komunikacyjnych opartych na TCP (PDF)

W tym bezpłatnym opracowaniu w formacie PDF porównano różne protokoły komunikacyjne oparte na protokole TCP (AMQP, OPC UA, MQTT, REST API), które sprawdziły się w działaniu i uznawane są za podstawę rozwiązań IIoT oraz Przemysłu 4.0. Pobierz bezpłatny dokument już teraz!

Moduł KE5 do szaf sterowniczych AS-Interface — łatwa obsługa i zarządzanie

Unikalna konstrukcja obudowy nowych modułów do szaf sterowniczych KE5 zapewnia ich doskonałą widoczność oraz ułatwia montaż, podłączanie przewodów oraz wykonywanie zadań konserwacyjnych w szafach sterowniczych i skrzynkach połączeniowych.

Gama produktów AS-Interface