Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem

Niedostępne do zakupu

Ten produkt został zastąpiony innym Przejdź do nowego produktu VBA-4E-G4-ZE
Niedostępne do zakupu
Niedostępne do zakupu

AS-Interface sensor module VAA-4E-G4-Z

VAA-4E-G4-Z
  • AS-Interface certificate
  • Degree of protection IP67
  • Flat or round cable connection (via standardized EMS base, not included with delivery)
  • Inputs for 2-wire sensors
  • Function display for bus and inputs
  • Lead monitoring of inputs that can be switched off selectively by channel

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  VAA-4E-G4-Z

Opis produktu
G4 module IP67
4 inputs (2-wire )
General specifications
Node typeStandard node
AS-Interface specificationV2.0
Required master specification≥ V2.0
UL File NumberE87056
Indicators/operating means
LED PWRAS-Interface voltage; LED green
LED IN4 dual LED yellow/red
yellow: switching state (input)
red: lead breakage
red and yellow: line short-circuit
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA
Protection classIII
Input
Number/Type4 inputs for 2-wire sensors, DC
Supplyfrom AS-Interface
Voltage15 V
Input current≤ 8 mA (limited internally)
Switching point
0 (unattenuated)≤ 1.5 mA
1 (attenuated)≥ 4.5 mA
Line fault detectionlead breakage: max. 0.5 mA
lead short-circuit: min. 5 mA
Compliance with standards and directives
Standard conformity
Degree of protectionEN 60529
Programming instructions
ProfileS-0.F
IO code0
ID codeF
Data bits (function via AS-Interface) input output
D0 IN1 -
D1 IN2 -
D2 IN3 -
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0lead monitoring IN1
P0 = 1 (default settings), monitoring deactivated
P0 = 0, monitoring activated
P1lead monitoring IN2
P1 = 1 (default settings), monitoring deactivated
P1 = 0, monitoring activated
P2lead monitoring IN3
P2 = 1 (default settings), monitoring deactivated
P2 = 0, monitoring activated
P3lead monitoring IN4
P3 = 1 (default settings), monitoring deactivated
P3 = 0, monitoring activated
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP67
Connectioncable piercing method or terminal compartment
yellow flat cable or standard round cable
inputs: M12 x 1.5 cable gland and cage tension spring terminals
Mass180 g
MountingDIN rail or screw mounting

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-4E-G4-Z

Product Documentation: VAA-4E-G4-Z

Language Selection:
Brief InstructionsJęzykTyp plikuRozmiar pliku
Instruction leaflet / BeipackzettelALLPDF206 KB

Design / Simulation: VAA-4E-G4-Z

Language Selection:
CADJęzykTyp plikuRozmiar pliku
CAD 3-D / CAD 3-DALLSTP2960 KB

Produkty powiązane: VAA-4E-G4-Z

Matching System Components

AS-Interface module mounting base with adressing jack for connection to flat cable (AS-Interface)fa
AS-Interface module mounting base for connection to flat cable (AS-Interface)fa
Accessories

AS-Interface Handheld with accessoryfa
Blind plug M12fa
Pobierz bezpłatnie: Opracowanie na temat protokołów komunikacyjnych opartych na TCP (PDF)

W tym bezpłatnym opracowaniu w formacie PDF porównano różne protokoły komunikacyjne oparte na protokole TCP (AMQP, OPC UA, MQTT, REST API), które sprawdziły się w działaniu i uznawane są za podstawę rozwiązań IIoT oraz Przemysłu 4.0. Pobierz bezpłatny dokument już teraz!

Moduł KE5 do szaf sterowniczych AS-Interface — łatwa obsługa i zarządzanie

Unikalna konstrukcja obudowy nowych modułów do szaf sterowniczych KE5 zapewnia ich doskonałą widoczność oraz ułatwia montaż, podłączanie przewodów oraz wykonywanie zadań konserwacyjnych w szafach sterowniczych i skrzynkach połączeniowych.

Gama produktów AS-Interface

Zapoznaj się z pełną gamą naszych produktów AS-Interface.