Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem

I/O hub IO-Link ICA-16IO-G20-IO-P16

ICA-16IO-G20-IO-P16
  • 16 digital inputs/outputs can be configured
  • Configuration and control via IO-Link
  • IO-Link Class A
  • LED for switching state and fault indication
  • Supply from IO-Link
  • IO-Link 1.1.3

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  ICA-16IO-G20-IO-P16

Opis produktu
G20 IO-Link module for 16 freely configurable digital inputs/outputs
General specifications
MTBF149 a
Indicators/operating means
LED green<--, -->: IO1..8 / IO9..16 bank indication
LED yellow/redIO1 ... IO16: inputs/outputs status, IO-Link status
Electrical specifications
Operating voltage18 ... 30 V DC, PELV
Current limitation of the supply max. 4 A
No-load supply current≤ 25 mA
Operating currentmax. 4 A
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Outputs 2 Byte
- Output signals 16 Bit
Vendor ID1 (0x0001)
Device ID985345 (0x0F0901)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Input
Number/Type16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16)
Supplyfrom IO-Link
Current loading capacity200 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Output
Number/Type16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof
Supplyfrom IO-Link
Voltage≥ (UB - 1.5 V)
Current200 mA per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Conformity
Communication interfaceIEC 61131-9:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 61131-9:2013
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.3
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
Ambient conditions
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree2
Mechanical specifications
Degree of protectionIP54 according to EN 60529
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Mass310 g
Dimensions
Height27.5 mm
Width131.5 mm
Length54 mm
Mounting2 clips with ∅ 8 mm drill hole
The module must be secured to a solid, continuous surface using the two lugs
Cable length1 m (IO-Link)
0.2 m (IO1/2, IO15/16), 0.3 m (IO3/4, IO13/14)
0.4 m (IO5/6, IO11/12); 0.5 m (IO7/8, IO9/10)
max. 10 m

Classifications

SystemClasscode
ECLASS 13.027242602
ECLASS 12.027242602
ECLASS 11.027242602
ECLASS 10.0.127242602
ECLASS 9.027242602
ECLASS 8.027242602
ECLASS 5.127242602
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16IO-G20-IO-P16

Function

The ICA-16IO-G20-IO-P16 is an IO-Link field module with 16 freely configurable digital inputs/outputs. The compact housing can be mounted directly in support profiles or cable ducts.

The module and the inputs and outputs are supplied with voltage via IO-Link.

The inputs and outputs are connected via cable outlets with 4-pin M8 sockets. IO-Link is connected via a cable outlet with 4-pin M12 connector.

The current switching state or an overload of the inputs or outputs is indicated via the IN or OUT LEDs.

Product Documentation: ICA-16IO-G20-IO-P16

Language Selection:
ManualsJęzykTyp plikuRozmiar pliku
ManualENGPDF635 KB

Approvals: ICA-16IO-G20-IO-P16

Language Selection:
CertificatesNr. certyfikatuJęzykTyp plikuRozmiar pliku
IO-Link Manufacturer DeclarationCERT-7194ALLPDF173 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-7463_POLPOLPDF195 KB
UK Declaration of Conformity (P+F)TDOC-7464_ENGENGPDF171 KB

Software: ICA-16IO-G20-IO-P16

Language Selection:
Device Description Files/DriversInformacja o wersjiTyp plikuRozmiar pliku
IODD / IODDV1.01.001 / 2023-11-21ZIP228 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB

Produkty powiązane: ICA-16IO-G20-IO-P16

Accessories
Mounting aidfa
Pobierz bezpłatnie: Opracowanie na temat protokołów komunikacyjnych opartych na TCP (PDF)

W tym bezpłatnym opracowaniu w formacie PDF porównano różne protokoły komunikacyjne oparte na protokole TCP (AMQP, OPC UA, MQTT, REST API), które sprawdziły się w działaniu i uznawane są za podstawę rozwiązań IIoT oraz Przemysłu 4.0. Pobierz bezpłatny dokument już teraz!

Moduł KE5 do szaf sterowniczych AS-Interface — łatwa obsługa i zarządzanie

Unikalna konstrukcja obudowy nowych modułów do szaf sterowniczych KE5 zapewnia ich doskonałą widoczność oraz ułatwia montaż, podłączanie przewodów oraz wykonywanie zadań konserwacyjnych w szafach sterowniczych i skrzynkach połączeniowych.

Gama produktów AS-Interface

Zapoznaj się z pełną gamą naszych produktów AS-Interface.