Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
Termék leírása |
---|
AS-Interface power supply, data decoupling, 8 A |
General specifications | ||
---|---|---|
UL File Number | E223176 | |
MTBF | 100 a | |
Indicators/operating means | ||
Reset push-button switch | FUSE mode reset | |
Power selection switch | changeover switch for 115 V AC/230 V AC | |
LED Overload | red LED, flashes in the FUSE mode | |
LED IR on | red LED: ON: Plug-in jumper position 2-3 OFF: Plug-in jumper position 1-2 |
|
Plug-in jumper | Position 1-2: Communication Mode Position 2-3: IR addressing |
|
LED AS-i ok | operating display; LED green | |
Electrical specifications | ||
Fusing | T8A/250 V AC HBC (not accessible) | |
Capacity factor | > 0.5 | |
Rated operating voltage | nominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable) permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC |
|
Rated operating current | 6,0 A (Switch position 115 V) 2.8 A (Switch position 230 V) |
|
Supply frequency | 47 ... 63 Hz or DC | |
Efficiency | typ. 92 % (at 230 V AC/8 A) | |
Surge protection | limited to max. 55 V | |
Output | ||
Short-circuit protection/overload | FUSE Mode (2 ... 5 s current, then trips) | |
Current limit | > 8.4 A | |
Voltage | 30.55 V DC ± 3 % | |
Current | 8 A | |
Galvanic isolation | overvoltage category III | |
Residual ripple | ≤ 50 mVss (500 kHz bandwidth, 50-Ω-measurement with ohmic load) | |
Short-circuit current | 12 ... 25 A (max. 5 s) | |
Standard conformity | ||
Electromagnetic compatibility | emitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022) noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11 |
|
Ambient conditions | ||
Ambient temperature | -10 ... 70 °C (14 ... 158 °F) (Measured 25 mm below the device) from 60° C 6W/°C power recovery necessary |
|
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 according to EN 60529 | |
Protection class | 1 (IEC 60536); Protective conductor connection necessary | |
Connection | Connection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2 fixed: 0.5 ... 6 mm2 stripped length 7 mm, connector sleeves are permissible |
|
Material | ||
Housing | metal | |
Mass | approx. 890 g | |
Dimensions | ||
Height | 124 mm | |
Width | 91 mm | |
Length | 102 mm |
System | Classcode |
---|---|
ECLASS 13.0 | 27040301 |
ECLASS 12.0 | 27040301 |
ECLASS 11.0 | 27040301 |
ECLASS 10.0.1 | 27040301 |
ECLASS 9.0 | 27040301 |
ECLASS 8.0 | 27040301 |
ECLASS 5.1 | 27040301 |
ETIM 9.0 | EC002540 |
ETIM 8.0 | EC002540 |
ETIM 7.0 | EC002540 |
ETIM 6.0 | EC002540 |
ETIM 5.0 | EC002540 |
UNSPSC 12.1 | 39121004 |
The primary pulsed DIN rail power pack is used for special power supply of AS-Interface networks via a two-wire line. It supplies a fully loaded AS-Interface system with an output current of 8 A.
The voltage input range of the device can be selected on the front side. This makes it possible to operate the device on all single-phase power supply voltages commonly used worldwide.
Certification of the device according to international and various national standards allows for worldwide usage.
Safe operation using FUSE mode:
To protect against overload and excess temperature, the device has a FUSE mode (electronically simulated fuse), for permanent shutoff of the output in the event of failure. This turns off the device in the event of overload, short circuit or excess temperature, thus protecting the AS-Interface cable and the attached components. A flashing LED indicates that the FUSE mode has been triggered. Turning the device on again requires deliberately pressing a Reset button on the front side of the unit. This prevents unwanted startup from occurring.
Operation without the AS-Interface string:
This AS-Interface power pack has an inductive output. For operation without the AS-Interface string (for example lab measurements) we recommend connecting a 470 μF/35 V capacitor between AS-Interface + and AS-Interface -. Standard commercial laboratory loads frequently tend to oscillate and together with the data decoupling form a resonance that exceeds the permitted modulation voltage.
Brief Instructions | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 181 KB | |
Manual / Handbuch | ALL | 86 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 10419 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 40 KB |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
US CA UL | CoC E223176 RptRef E223176-20070416 | ALL | 444 KB | |
US CA UL | E223176 | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-4814A | ALL | 163 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|