Ipari érzékeléstechika
+36 88 545 902
+36 88 560 472
Leválasztók, jelátalakítók
+36 88 545 902
+36 88 560 472

Switch Amplifier KFD2-SH-Ex1

KFD2-SH-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for approved dry contacts or SN/S1N sensors
  • Relay contact output
  • Fault indication output
  • Line fault detection (LFD)
  • Up to SIL 3 acc. to IEC/EN 61508
  • Up to PL d acc. to EN/ISO 13849

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  KFD2-SH-Ex1

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL d
Supply
ConnectionPower Rail or terminals 22+, 23+, 24-
Rated voltage20 ... 35 V DC
Ripple≤ 10 %
Rated current≤ 130 mA
Power dissipation2.1 W
Power consumptionmax. 2.3 W
Input
Connection sidefield side
Connectionterminals 10+, 12-
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistance≤ 50 Ω, in hazardous area cable capacitances and inductivities are to be taken into account
Switching point
Relay de-energizedI < 2.1 mA and I > 5.9 mA
Relay energized2.8 mA < I < 5.3 mA
Response delay≤ 1 ms
Output
Connection sidecontrol side
Connectionoutput I: terminals 13, 14 ; output II: terminals 15, 21 ; output III: terminals 16+, 17-
Output Irelay , signal
Contact loading50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load
Mechanical life50 x 106 switching cycles
Output IIrelay , signal
Contact loading50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load
Mechanical life50 x 106 switching cycles
Output IIIelectronic output, passive , fault signal
Rated voltage10 ... 30 V DC
Signal level1-signal: (L+) -2.5 V (7 mA, short-circuit proof) / 0-signal: blocked output
(Leakage current ≤ 10 µA)
Transfer characteristics
Switching frequency5 Hz
Galvanic isolation
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Machinery Directive
Directive 2006/42/ECEN/ISO 13849-1:2015
Conformity
Electromagnetic compatibilityNE 21:2017 , EN 61326-3-1:2017
Degree of protectionIEC 60529:2001
SafetyIEC/EN 61508:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 280 g
Dimensions40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) (W x H x D) , housing type C1
Height107 mm
Width40 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2042
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Voltage9.56 V
Current16.8 mA
Power41 mW (linear characteristic)
Supply
Maximum safe voltage40 V AC/DC (Attention! The rated voltage can be lower.)
Output
Maximum safe voltageoutput I/output II: 253 V AC/DC (Attention! Um is no rated voltage.)
output III: 60 V AC/DC (Attention! Um is no rated voltage.)
CertificateTÜV 99 ATEX 1493 X
MarkingEx-Hexagon II 3G Ex ec nC IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
FM approval
Control drawing116-0158
IECEx approval
IECEx certificateIECEx TUN 19.0013X
IECEx markingEx ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SH-Ex1

Function

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals (SN/S1N proximity sensors or approved dry contacts) from a hazardous area to a safe area.

The input controls one relay contact output with 3 NO contacts (one output is in series to the both output relays for the safety function), one relay contact output with one NO contact, and one passive transistor output.

Unlike an SN/S1N series proximity sensor, a mechanical contact, requires a 10 kΩ resistor to be placed across the contact in addition to a 1.5 kΩ resistor in series.

Lead breakage (LB) and short circuit (SC) conditions of the control circuit are continuously monitored.

During an fault condition, the fault indication output energizes and outputs I and II de-energize.

For safety applications up to SIL3, output I must be used. For safety applications up to SIL2, output I and output II can be used.

Informative Literature: KFD2-SH-Ex1

Nyelvválasztás:
LiteratureNyelvFájltípusFájlméret
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-SH-Ex1

Nyelvválasztás:
Safety and Security DocumentationNyelvFájltípusFájlméret
Használati útmutatóHUNPDF166 KB
Functional Safety ManualENGPDF1965 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-SH-Ex1

Nyelvválasztás:
CADNyelvFájltípusFájlméret
CAD 3-D / CAD 3-DALLSTP186 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ87 KB

Approvals: KFD2-SH-Ex1

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
Europe PTB ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GPTB 00 ATEX 2042ALLPDF513 KB
Europe TUV II 3 GTÜV 99 ATEX 1493XALLPDF2538 KB
Japan TIISTC16173ALLPDF1623 KB
South Africa MASCMASC S/22-8373XALLPDF715 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 19.0013XALLLINK---
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 23UKEX2155ALLPDF167 KB
Worldwide TÜV SÜD Functional Safety AssessmentPM85769TALLPDF797 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF71 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0075EALLPDF111 KB

Kapcsolódó termékek: KFD2-SH-Ex1

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Funkcionális biztonság központ a Pepperl+Fuchs-nál

Több száz SIL/PL értékeléssel ellátott termék, ingyenes eszközök és prospektusok egy helyen: a „Funkcionális biztonság központ” a legjobb kiindulópont biztonsági funkciók kivitelezéséhez.

K-System by Pepperl+Fuchs: Globally certified protection for people, plants, and the environment!

The largest portfolio of its kind: K-System components and systems are established in process industries around the world. Learn more!