AS-Interface Gateway/Safety Monitor VBG-ENX-K30-DMD-S16

VBG-ENX-K30-DMD-S16
  • Gateway and safety monitor in one housing
  • Gateway compliant with AS-Interface specification 3.0
  • Connection to Ethernet Modbus TCP/IP
  • AS-Interface safety monitor with extended range of functions
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • Memory card for configuration data
  • 2 AS-Interface networks
  • 2 safe output relays and 2 safe electronic outputs
  • Integrated switch allows line topology
  • DLR technology supports ring topology

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  VBG-ENX-K30-DMD-S16

Termék leírása
EtherNet/IP + Modbus TCP Gateway with integrated safety monitor, double master for 2 AS-Interface networks
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
B10d2 E+7
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED ETHERNETethernet active; LED green
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRJ MODEprojecting mode active; LED yellow
LED U AS-iAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuitOutput circuit closed; 4 x green LEDs
Button4
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
Rated operating current≤ 300 mA off AS interface network 1
≤ 300 mA off AS interface network 2
≤ 370 mA in total
Interface 1
Interface type2 x RJ-45
ProtocolEtherNet/IP + MODBUS TCP/IP acc. to IEEE 802.3
supports device level ring protocol DLR
Transfer rate10 MBit/s / 100 MBit/s , Automatic baud rate detection
Interface 2
Interface typeRS 232, serial
Diagnostic Interface
Transfer rate19,2 kBit/s
Interface 3
Interface typeChip card slot
Input
Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Output
Safety outputmax. contact load:
Output circuits 1 and 2: 2 potential-free contacts,
3  ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
0.5  ADC-13 at 30  VDC
Connection
EthernetRJ-45
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Shock resistanceEN 61131-2:2004
StandardsEN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
Approvals and certificates
UL approvalAn isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Mass800 g
Dimensions
Height120 mm
Width110 mm
Length89 mm
Construction typeLow profile housing , Stainless steel

Classifications

SystemClasscode
ECLASS 13.027242607
ECLASS 12.027242607
ECLASS 11.027242607
ECLASS 10.0.127242607
ECLASS 9.027242607
ECLASS 8.027242607
ECLASS 5.127242607
ETIM 9.0EC001603
ETIM 8.0EC001603
ETIM 7.0EC001603
ETIM 6.0EC001603
ETIM 5.0EC001603
UNSPSC 12.139121004

Details: VBG-ENX-K30-DMD-S16

Function

The VBG-ENX-K30-DMD-S16 is an Ethernet/IP+Modbus TCP gateway with an integrierted safety monitor and a double master according to AS-Interface specification 3.0 with a degree of protection IP20.

The device is a gateway with full functionality combined with a safety monitor. The gateway connects an AS-Interface system to a higher-level Ethernet or Modbus protocol. It acts as a master for the AS-Interface segment and as a slave for Ethernet / Modbus. During cyclic data exchange, the digital data of an AS-Interface segment is transferred. Analog values as well as the complete command set of the new AS-Interface specification are transferred via Ethernet / Modbus using a command interface.

The gateway has four inputs and four outputs. The four inputs are used either for extended EDM device monitoring or as start inputs. Two sets of two outputs act as relay outputs and switch output circuits 1 and 2 and, as semiconductor outputs, output circuits 3 and 4. The K30 model is particularly suitable for installation in a control cabinet.

Configuration of the device can be performed using switches. Seven LED located on the front panel indicate the current status of the AS-Interface segment. One LED shows the power supply via AUX. A further eight LEDs indicate the status of the inputs and outputs.

With the graphical display, the commissioning of the AS-Interface circuits and testing of the connected peripherals can take place completely separately from the commissioning of the higher-level network and the programming. With the 4 switches, all functions can be controlled and visualized on the display.

The device has a card slot for a memory card for the storage of configuration data.

An integrated Switch and 2 RJ-45 sockets allow the design of a line topology without the use of an external Switch.

The device level ring protocol DLR increases the reliability of a ring topology at the device level, thus optimizing the machine running times.

An integrated webserver allows to administrate the device and The AS-interface network without additional hard and/or software via a browser interface.

The redundant power supply guarantees that the double master remains in function and is diagnosticable, when a failure of a power supply unit in one of the two AS-interfaces circles occures. Also communication with the superior field bus is not disturbed by the failure of a power supply.

Informative Literature: VBG-ENX-K30-DMD-S16

Nyelvválasztás:
LiteratureNyelvFájltípusFájlméret
Application Report - Safe and Efficient AS-Interface Installation at JOTONENGPDF1990 KB

Product Documentation: VBG-ENX-K30-DMD-S16

Nyelvválasztás:
Product informationNyelvFájltípusFájlméret
Configuring a Safe Input on AS-Interface Safety at WorkENGPDF258 KB
Brief Instructions
Commissioning VBG-ENX-K20-DMD-S16 / Inbetriebnahme VBG-ENX-K20-DMD-S16ALLPDF1285 KB
Installation instructions VBG-ENX-K30-DMD-S16 / Montageanweisung VBG-ENX-K30-DMD-S16ALLPDF2113 KB
Manuals
Manual AS-Interface 3.0 Command InterfaceENGPDF3265 KB
Manual Control III Programming in C (small PLC)ENGPDF1276 KB
Manual VBG-ENX-K30-DMD-S16*ENGPDF7792 KB
Manual Web-InterfaceENGPDF1407 KB

Design / Simulation: VBG-ENX-K30-DMD-S16

Nyelvválasztás:
CADNyelvFájltípusFájlméret
CAD 3-D / CAD 3-DALLSTP4057 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VBG-ENX-K30-DMD-S16

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
AS-International Association AS-Interface125001ALLPDF118 KB
US CA ULE223772ALLLINK---
Worldwide AS-International Association AS-Interface93201ALLPDF636 KB

Kapcsolódó termékek: VBG-ENX-K30-DMD-S16

Accessories
Interface converter USB/RS 232fa
Software for configuration of K30 Master Monitors/K31 and KE4 Safety Monitorsfa
Interface cable for connecting the K30/K31 Safety Monitor to a PCfa
Ingyenes letöltés: Tanulmány a TCP-alapú kommunikációs protokollokról (PDF)

Ebben az ingyenes PDF tanulmányban összehasonlítjuk a különböző TCP-alapú kommunikációs protokollokat (AMQP, OPC UA, MQTT, REST API), amelyek kimagaslanak a mezőnyből és amiket az IIoT-t és az Ipar 4.0-t lehetővé tevő technológiaként tartanak számon. Töltse le ingyenesen most!

AS-Interfész termékkínálat

Tekintse meg az AS-Interfész termékek teljes választékát!