国を選択してください
KFU8-GUT-Ex1.D Temperature Converter
Temperature converter with limit values
主なメリットの概要
- 1-channel isolated barrier
- Universal usage at different power supplies
- Thermocouple, RTD, potentiometer or voltage input
- Redundant TC input
- Current output 0/4 mA ... 20 mA
- 2 relay contact outputs
- Configurable by PACTware or keypad
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
もっと見る






注記
Pepperl+Fuchs GmbH または Pepperl+Fuchs AG の名義で、会社形態の変更前に発行された証明書、適合宣言書などの製品関連文書はすべて、Pepperl+Fuchs SE に対しても有効です。
EN
- EN
- DE
- ES
- FR
- PL
KFU8-GUT-Ex1.Dの技術データ
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 23, 24 | |
| Rated voltage | Ur | 20 ... 90 V DC / 48 ... 253 V AC |
| Power dissipation/power consumption | ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA |
| Programming interface | programming socket |
| Connection side | field side | ||||||||||
| Connection | terminals 1, 2, 3, 4, 6 | ||||||||||
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | ||||||||||
| |||||||||||
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | ||||||||||
| |||||||||||
| Potentiometer | 0.8 ... 20 kΩ | ||||||||||
| |||||||||||
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | ||||||||||
| Input resistance | ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) | ||||||||||
| Measuring current | approx. 400 µA with resistance measuring sensor | ||||||||||
| Connection side | control side | |||||||||||||
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |||||||||||||
| Output I, II | relay | |||||||||||||
| ||||||||||||||
| Output III | Analog current output | |||||||||||||
| ||||||||||||||
| Deviation | ||||||||||||||||||||
| ||||||||||||||||||||
| Sampling rate | approx. 700 ms | |||||||||||||||||||
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 | ||||||||||
| Connection | screw terminals | ||||||||||
| Mass | 300 g | ||||||||||
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||||||||||
| |||||||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||||||
| EU-type examination certificate | TÜV 03 ATEX 2140 | |||||||||||||||||||
| ||||||||||||||||||||
| Supply | ||||||||||||||||||||
| ||||||||||||||||||||
| Input | terminals 2, 6 (for active equipment) | |||||||||||||||||||
| ||||||||||||||||||||
| Inputs | terminals 1, 2, 3, 4, 6 (for passive equipment) | |||||||||||||||||||
| ||||||||||||||||||||
| Analog output | ||||||||||||||||||||
| ||||||||||||||||||||
| Interface | ||||||||||||||||||||
| ||||||||||||||||||||
| Galvanic isolation | ||||||||||||||||||||
| ||||||||||||||||||||
| Directive conformity | ||||||||||||||||||||
| ||||||||||||||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
関連ページ