KCD2-SCD-Ex1.ES SMART Current Driver
主なメリットの概要
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Current output up to 650 Ω load
- HART-IP and valve positioner
- Line fault detection (LFD)
- Housing width 12.5 mm
- Up to SIL 3 acc. to IEC/EN 61508
もっと見る






注記
Pepperl+Fuchs GmbH または Pepperl+Fuchs AG の名義で、会社形態の変更前に発行された証明書、適合宣言書などの製品関連文書はすべて、Pepperl+Fuchs SE に対しても有効です。
EN
- EN
- DE
- ES
- FR
- PL
KCD2-SCD-Ex1.ESの技術データ
| Signal type | Analog output |
| Safety Integrity Level (SIL) | SIL 3 |
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | Ur | 19 ... 30 V DC |
| Ripple | ≤ 10 % | |
| Rated current | Ir | ≤ 33 mA at 24 V |
| Power dissipation | ≤ 700 mW at 20 mA and 500 Ω load | |
| Power consumption | ≤ 800 mW |
| Connection side | control side | |
| Connection | terminals 5-, 6+ | |
| Input signal | 4 ... 20 mA , limited to approx. 25 mA | |
| Input voltage | open loop voltage of the control system < 30 V, in line fault mode < 60 V | |
| Voltage drop | approx. 6 V at 20 mA | |
| Input resistance | > 100 kΩ, with field wiring open or < 50 Ω |
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Voltage | ≥ 13 V at 20 mA | |
| Current | 4 ... 20 mA | |
| Load | 100 ... 650 Ω | |
| Ripple | 20 mV rms | |
| Line fault detection | field wiring open or < 50 Ω and test current < 2 mA |
| Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis | ||||
| |||||
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) | ||||
| Rise time | 10 to 90 % ≤ 10 ms | ||||
| Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 | |
| Degree of protection | IEC 60529 | |
| Protection against electrical shock | UL 61010-1:2012 |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | CESI 20 ATEX 016 X | ||||||||||||||||
| |||||||||||||||||
| Supply | |||||||||||||||||
| |||||||||||||||||
| Equipment | terminals 1+, 2- | ||||||||||||||||
| |||||||||||||||||
| Certificate | CESI 20 ATEX 017 X | ||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| UL approval | E106378 | |||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |