FB6306B3 Relay Output

주요 혜택 한눈에 보기

  • 8-channel
  • Installation in suitable enclosures in Zone 1
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Outputs with Ex e terminals

더 보기

Product Compliance: Europe – CE
Approval symbol
참고

Pepperl+Fuchs GmbH 또는 Pepperl+Fuchs AG 명의로 전환 이전에 발행된 인증서, 적합성 선언서 등 모든 제품 관련 서류는 Pepperl+Fuchs SE에도 적용됩니다.

EN
  • EN
  • DE

FB6306B3 기술 데이터

Occupied slots2
Connectionbackplane bus
Rated voltageUr12 V DC +4/-2 % , only in connection with the power supplies FB92**
Power dissipation1.9 W
Power consumption1.4 W
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Number of channels8
Field device interface
ConnectionRelay output
Connectionchannel I: 1-2 NO; channel II: 3-4 NO; channel III: 5-6 NO; channel IV: 7-8 NO; channel V: 9-10 NO; channel VI: 11-12 NO; channel VII: 13-14 NO; channel VIII: 15-16 NO
Relay
Switching voltage30 V DC
Switching current1 A DC
Switch power30 W
Minimum load5 V 10 mA
Electrical life0.1 million switching cycles at maximum load and temperature
Contact MaterialAgPd gold plated
Response time20 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: Communication error or active safety shutdown , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-8) yellow: Channel status
Codingoptional mechanical coding via front socket
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Low voltage
Directive 2014/35/EUEN 61010-1 , EN 60664-1
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Relative humidityEN 60068-2-78
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Altitudemax. 2000 m
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
ConnectionEx e spring terminal with protective cover
Massapprox. 945 g
Dimensions
Height107 mm
Width57 mm
Depth132 mm
EU-type examination certificateFIDI 23 ATEX 0077 U
MarkingEx-Hexagon II 2G Ex db eb q IIC Gb
Galvanic isolation
Output/power supply, internal busbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC
Directive conformity
Directive 2014/34/EUEN IEC 60079-0
EN 60079-1
EN 60079-5
EN 60079-7
ATEX approvalFIDI 23 ATEX 0077 U
IECEx approval
IECEx certificateIECEx FIDI 23.0009U
IECEx markingEx db eb q IIC Gb
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
일반 참고 사항