국가 선택
ICA-16IO-G20-IO-P16 IO-Link I/O Hub
G20 IO-Link I/O Hub for 16 freely configurable digital inputs/outputs
주요 혜택 한눈에 보기
- 16 digital inputs/outputs can be configured
- Configuration and control via IO-Link
- IO-Link Class A
- LED for switching state and fault indication
- Supply from IO-Link
- IO-Link 1.1.3
더 보기









참고
Pepperl+Fuchs GmbH 또는 Pepperl+Fuchs AG 명의로 전환 이전에 발행된 인증서, 적합성 선언서 등 모든 제품 관련 서류는 Pepperl+Fuchs SE에도 적용됩니다.
EN
- EN
- DE
- FR
ICA-16IO-G20-IO-P16 기술 데이터
| UL File Number | E223772 | |
| MTBF | 149 a |
| LED green | <--, -->: IO1..8 / IO9..16 bank indication | |
| LED yellow/red | IO1 ... IO16: inputs/outputs status, IO-Link status |
| Operating voltage | UB | 18 ... 30 V DC, PELV Current limitation of the supply max. 4 A |
| No-load supply current | I0 | ≤ 25 mA |
| Operating current | IB | max. 4 A |
| Interface type | IO-Link | |
| IO-Link revision | 1.1 | |
| Device profile | Identification and Diagnosis - I&D Firmware update | |
| Process data | Inputs 3 Byte - Input signals 16 Bit - diagnosis signals 5 Bit Outputs 2 Byte - Output signals 16 Bit | |
| Vendor ID | 1 (0x0001) | |
| Device ID | 985345 (0x0F0901) | |
| Data transfer rate | COM3 (230.4 kbits/s) | |
| Min. cycle time | 1 ms | |
| SIO mode support | no | |
| Compatible master port type | Class A |
| Number/Type | 16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16) | |
| Supply | from IO-Link | |
| Current loading capacity | 200 mA , overload and short-circuit protected | |
| Input current | ≤ 5 mA (limited internally) | |
| Switching point | Type 3 according to IEC 61131-2 |
| Number/Type | 16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof | |
| Supply | from IO-Link | |
| Voltage | ≥ (UB - 1.5 V) | |
| Current | 200 mA per output |
| Electromagnetic compatibility | |||||
| |||||
| Degree of protection | EN 60529:2000 | |
| Input | EN 61131-2:2007 | |
| Communication interface | IEC 61131-9:2013 / IO-Link V1.1.3 | |
| Emitted interference | EN 61000-6-4:2007 | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 |
| UL approval | UL 61010-1, UL 61010-2-201 Load specification DC General Use / DC Pilot Duty Degree of protection not tested by UL; tested by Pepperl+Fuchs SE |
| Ambient temperature | -30 ... 70 °C (-22 ... 158 °F) | |
| Storage temperature | -30 ... 85 °C (-22 ... 185 °F) | |
| Relative humidity | 85 % non-condensing | |
| Climatic conditions | For indoor use only | |
| Altitude | ≤ 5000 m above MSL | |
| Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
| Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz | |
| Pollution degree | 2 |
| Degree of protection | IP67 according to EN 60529 | ||||||||||
| Connection | IO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded) Female connector: LF type or similar IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded) Mating connector: LM type or similar | ||||||||||
| Mass | 310 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Mounting | 2 clips with ∅ 8 mm drill hole The module must be secured to a solid, continuous surface using the two lugs | ||||||||||
| Cable length | 1 m (IO-Link) 0.2 m (IO1/2, IO15/16), 0.3 m (IO3/4, IO13/14) 0.4 m (IO5/6, IO11/12); 0.5 m (IO7/8, IO9/10) max. 10 m | ||||||||||
관련 페이지
더 많은 정보를 찾고 계신가요? 관련 페이지에서 자유롭게 자세히 알아보세요.