국가 선택
HD2-GTR-4PA.PN GatewayFieldConnex® Fieldbus
Gateway module for fieldbus power hub for PROFINET to PROFIBUS PA communication
주요 혜택 한눈에 보기
- Gateway PROFINET RT to 4 x PROFIBUS PA segments
- Up to 32 devices per PROFIBUS PA segment
- Installation in Zone 2/Class I, Div. 2
- Ring and system redundancy
- Integrated webserver for diagnostics
더 보기






참고
Pepperl+Fuchs GmbH 또는 Pepperl+Fuchs AG 명의로 전환 이전에 발행된 인증서, 적합성 선언서 등 모든 제품 관련 서류는 Pepperl+Fuchs SE에도 적용됩니다.
EN
- EN
- DE
HD2-GTR-4PA.PN 기술 데이터
| Design / Mounting | Motherboard based | |
| Installation in hazardous area | Zone 2 / Div. 2 |
| Rated voltage | Ur | 19.2 ... 35 V SELV/PELV |
| Rated current | Ir | typ. 135 mA |
| Power dissipation | approx. 3.5 W |
| Number of segments | 4 | |
| Number of devices per segment | max. 32 | |
| Fieldbus type | PROFIBUS PA |
| Number of ports | 2 | |
| Protocol | PROFINET | |
| Ethernet Interface | Connector plug , 2x RJ45 | |
| Transfer rate | 100 MBit/s | |
| Redundancy | Ring (MRP) , System S2 |
| LED ETH1 LINK 2 | green: link status | |
| LED ETH1 ACT | yellow: activity status | |
| LED ETH2 LINK | green: link status | |
| LED ETH2 ACT | yellow: activity status | |
| LED ERR | red 2 Hz flashing: Ethernet error | |
| LED Seg 1...4 | red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error | |
| LED PWR | green: Power on | |
| LED DP/ERR | red 2 Hz flashing: DP error ; red: Hardware error | |
| LED Red. | yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available |
| CH/PROFIBUS DP | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
| PROFIBUS DP/Supply | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
| CH/CH | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
| CH/Ethernet | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
| All circuits/FE | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
| Ethernet/Supply | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) vertically mounted , -40 ... 70 °C (-40 ... 158 °F) horizontally mounted | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | < 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| Housing material | Polycarbonate | ||||||||||
| Degree of protection | IP20 | ||||||||||
| Mass | 250 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Mounting | motherboard mounting | ||||||||||
| Certificate | TÜV 15 ATEX 7735 X | ||||
| |||||
| Directive conformity | |||||
| |||||
| IECEx approval | IECEx TUR 16.0007X | ||||
| |||||
| Marine approval | pending |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |