VAA-4E4A-KE-ZE/R 기술 데이터
| Node type | Standard node | |||||||||||||
| AS-Interface specification | V2.1 | |||||||||||||
| Required gateway specification | ≥ V2.0 | |||||||||||||
| Profile | S-7.0 | |||||||||||||
| ||||||||||||||
| UL File Number | E106378 | |||||||||||||
| LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply | |
| LED INT | Internal input supply active; LED green | |
| LED PWR | AS-Interface voltage; LED green | |
| LED IN | switching state (input); 4 LED yellow | |
| LED OUT | Switching state (output); 4 LED yellow |
| Auxiliary voltage (input) | UEXT | 12 ... 30 V DC PELV |
| Rated operating voltage | Ue | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | Ie | ≤ 35 mA (no sensors)/max. 210 mA |
| Surge protection | O1 ... O4: Over voltage category II UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |||||||
| Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) | |||||||
| Voltage | 21 ... 31 V DC (INT) | |||||||
| Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) | |||||||
| Input current | ≤ 8 mA (limited internally) | |||||||
| Switching point | according to DIN EN 61131-2 (Type 2) | |||||||
| ||||||||
| Signal delay | < 2 ms (input/AS-Interface) | |||||||
| Number/Type | 4 relay outputs, normally open | |||||||
| Supply | none | |||||||
| Nominal load | ||||||||
| ||||||||
| Control circuit | ≤ 8 mA per relay (from AS-Interface) | |||||||
| Switching delay | < 10 ms (AS-Interface/contact) | |||||||
| Usage category | DC-13 and AC-14 | |||||||
| Switching | ||||||||
| ||||||||
| Overload protection | fuse unit 2 A required in the load current circuit | |||||||
| Input/Output | safe isolation, rated insulation voltage 300 V AC | |
| Input/AS-Interface | Switch position INT: None Switch position EXT: reinforced insulation, rated insulation voltage 66 V DC | |
| Output/Output | basic insulation, rated insulation voltage 300 V AC | |
| Output/AS-Interface | safe isolation, rated insulation voltage 300 V AC |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Galvanic isolation | EN 60664-1:2007 | |
| Electromagnetic compatibility | NAMUR NE 21: 1998-08 | |
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | EN 62026-2:2013 | |
| AS-Interface | EN 62026-2:2013 |
| Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 85 % , non-condensing | |
| Climatic conditions | For indoor use only | |
| Altitude | ≤ 2000 m above MSL | |
| Pollution degree | 2 |
| Degree of protection | IP20 | ||||||||||
| Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 | ||||||||||
| Material | |||||||||||
| |||||||||||
| Mass | 170 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Mounting | DIN mounting rail | ||||||||||
| Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm | ||||||||||