Wybierz kraj
VBA-4A-KE5-IJL/UJL ASi Analog Module
Switch cabinet module, 4 analog outputs
Najważniejsze zalety w skrócie
- Housing with push-in connection technology and mechanically coded terminal blocks
- Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
- Power supply of outputs external or from the module, as required
- Function indicator for the bus, external auxiliary voltage, internal output voltage, and outputs









Uwaga
Wszystkie dokumenty dotyczące produktów, takie jak certyfikaty, deklaracje zgodności itp., które zostały wydane przed przekształceniem pod nazwą Pepperl+Fuchs GmbH lub Pepperl+Fuchs AG, mają również zastosowanie do spółki Pepperl+Fuchs SE.
EN
- EN
- DE
- FR
Dane techniczne produktu VBA-4A-KE5-IJL/UJL
| Node type | Standard node | |
| AS-Interface specification | V3.0 | |
| Required gateway specification | ≥ V2.1 | |
| UL File Number | E223772 | |
| MTBF | 115 a |
| LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault | |
| LED INT | Internal output voltage active; green LED | |
| LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error | |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage | |
| LED OUT | Status of output signal; yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range |
| Auxiliary voltage (output) | UAUX | 24 V DC ± 15 % PELV |
| Rated operating voltage | Ue | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | Ie | ≤ 75 mA (without outputs) / max. 200 mA |
| Protection class | III | |
| Current consumption | IAUX ≤ 650 mA | |
| Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
| Number/Type | 4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V | |
| Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) | |
| Load | voltage output: min. 1 kΩ current output: max. 600 Ω | |
| Current loading capacity | ≤ 100 mA (signal current + actuator power supply) from AS-Interface; overload-proof and short-circuit proof ≤ 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof | |
| Resolution | Voltage output: 3 mV Current output: 6 µA | |
| Accuracy | 0.15 % of full-scale value | |
| Temperature influence | 1 µA/K or 0,3 mV/K | |
| Short-circuit current | voltage output: max. 22 mA |
| Electromagnetic compatibility | |||||
| |||||
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | EN 62026-2:2013 | |
| Emitted interference | EN 61000-6-4:2007 | |
| AS-Interface | EN 62026-2:2013 | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Profile | S-7.3.6 | |||||||||||||
| IO code | 7 | |||||||||||||
| ID code | 3 | |||||||||||||
| ID1 code | F | |||||||||||||
| ID2 code | 6 | |||||||||||||
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |||||||||||||
| Parameter bits (programmable via AS-i) | function | |||||||||||||
| ||||||||||||||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 85 % , non-condensing | |
| Climatic conditions | For indoor use only | |
| Altitude | ≤ 2000 m above MSL | |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
| Pollution degree | 2 |
| Degree of protection | IP20 | ||||||||||
| Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 | ||||||||||
| Material | |||||||||||
| |||||||||||
| Mass | 110 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Mounting | DIN mounting rail | ||||||||||
| Note | Max. length of jumpers = 5 cm | ||||||||||
Powiązane strony
Szukasz więcej informacji? Zapraszamy do zapoznania się z naszymi stronami poświęconymi tej tematyce.