Wybierz kraj
ICA-16DIO-G16-IO I/O Hub
I/O hub with IO-Link interface for 16 freely configurable digital inputs/outputs
Najważniejsze zalety w skrócie
- IO-Link Class A
- IO-Link 1.1.4
- LED for switching state and fault indication
- Configuration and control via IO-Link
- Supply from IO-Link
- 16 digital inputs/outputs can be configured
Pokaż więcej









Uwaga
Wszystkie dokumenty dotyczące produktów, takie jak certyfikaty, deklaracje zgodności itp., które zostały wydane przed przekształceniem pod nazwą Pepperl+Fuchs GmbH lub Pepperl+Fuchs AG, mają również zastosowanie do spółki Pepperl+Fuchs SE.
EN
- EN
- DE
- FR
Dane techniczne produktu ICA-16DIO-G16-IO
| MTBF | 134 a |
| LED PWR | LED green: flashing with short break (1 Hz) - IO-Link mode | |
| LED IO | Switch state (IO); multicolor LED yellow: only IO pin 4 is active blue: only IO pin 2 is active green: both IO pin 4 and pin 2 are active red: overload at sensor supply or output |
| Operating voltage | UB | 18 ... 30 V DC, PELV |
| No-load supply current | I0 | ≤ 30 mA |
| Operating current | IB | Total current of all inputs/outputs max. 3A (limited by fuse) |
| Interface type | IO-Link | |
| IO-Link revision | 1.1 | |
| Device profile | Identification and Diagnosis - I&D Firmware update | |
| Process data | Inputs 3 Byte - Input signals 16 Bit - diagnosis signals 5 Bit Outputs 2 Byte - Output signals 16 Bit | |
| Vendor ID | 1 (0x0001) | |
| Device ID | 985858 (0x0F0B02) | |
| Data transfer rate | COM3 (230.4 kbits/s) | |
| Min. cycle time | 1 ms | |
| SIO mode support | no | |
| Compatible master port type | Class A |
| Number/Type | 16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16) | |
| Supply | from IO-Link | |
| Current loading capacity | 180 mA , overload and short-circuit protected | |
| Input current | ≤ 5 mA (limited internally) | |
| Switching point | Type 3 according to IEC 61131-2 |
| Number/Type | 16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof | |
| Supply | from IO-Link | |
| Voltage | ≥ (UB - 1.5 V) | |
| Current | 180 mA per output |
| Electromagnetic compatibility | |||||
| |||||
| Degree of protection | EN 60529:2000 | |
| Input | EN 61131-2:2007 | |
| Communication interface | IEC 61131-9 / IO-Link V1.1.4 | |
| Emitted interference | EN 61000-6-4:2007 | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 |
| UL approval | E223772 Power limitation by fuse in accordance with UL248-1, UL248-14, rated current 3 A. Protection of the personnel and the plant is not ensured if the product is not being used according to its intended use. Load specification DC General Use / DC Pilot Duty Degree of protection not tested by UL; tested by Pepperl+Fuchs SE Units shall be connected using CYJV or PVVA cord having suitable ratings min.50 V, min 4 A, min. 100 °C. The product must be installed in accordance with local laws. The device shall be installed on non-flammable, straight surface. |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 85 % non-condensing | |
| Climatic conditions | For indoor use only | |
| Altitude | ≤ 5000 m above MSL | |
| Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
| Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz | |
| Pollution degree | 3 |
| Degree of protection | IP67 / IP68 / IP69k | |||||||||||||
| Connection | IO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded) Female connector: LF type or similar IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded) Mating connector: LM type or similar | |||||||||||||
| Material | ||||||||||||||
| ||||||||||||||
| Mass | 110 g | |||||||||||||
| Tightening torque, cable gland | 0.4 Nm (M12 connector), 0.2 Nm (M8 connector) | |||||||||||||
| Dimensions | ||||||||||||||
| ||||||||||||||
| Mounting | screw mounting | |||||||||||||
Powiązane strony
Szukasz więcej informacji? Zapraszamy do zapoznania się z naszymi stronami poświęconymi tej tematyce.